| Voltage and frequency protection The ARGUS 8 series of voltage and frequency
 relays are numerical, multi-function devices that are
 designed to be applied for the protection of
 transmission, distribution and industrial systems.
 ARGUS 8 can be used for load shedding and other
 protection purposes, and can provide phase under
 and over voltage, neutral displacement overvoltage,
 negative sequence overvoltage and under and
 overfrequency protection elements.
 ARGUS 8 is part of the comprehensive range of
 ARGUS-platform based numeric relays. These
 relays have extensive control functions, which are
 supplemented by advanced metering, data storage
 and fibre-optic communications. Supervisory and
 self monitoring features give added confidence to
 the user as well as reduced maintenance and down
 time. A menu-based interface gives user-friendly
 access to relay settings, meters and operational
 data.
 FEATURES
 • Each phase voltage element can be
 configured for undervoltage or overvoltage
 • With 2 or 3 phase measurement each
 element can be configured to require
 operation of any phase or all phases.
 • Negative sequence overvoltage with two
 elements
 • Neutral voltage displacement with two
 elements
 • Four independent frequency elements, each
 of which can be configured for
 underfrequency or overfrequency
 • Frequency elements can be blocked by
 voltage elements, enabling simple logic
 schemes
 • Independent definite time delays for each
 element
 • Modbus IEC 60870-5-103 protocol for
 communicating
 • Fibre optic or RS485 electrical
 communication
 • Fault, event & waveform recorder
 • Starter & trip LED Indication
 DESCRIPTION
 The protection functions available in ARGUS 8 have
 many possible applications, some of which are
 mentioned within the descriptions below.
 Undervoltage and overvoltage
 Four independent elements are supplied, each of
 which can be set to operate for undervoltage or
 overvoltage conditions and all having separate
 definite time delay elements. These can be used to
 protect generators against overvoltages, motors
 against loss of supply or applied as backup
 protection in the event of defective system
 regulating equipment.
 Negative sequence overvoltage
 Two independent elements are supplied, each of
 which has a definite time delay element. These can
 be used to monitor the quality of the supply and
 protect plant or feeders against system unbalance.
 Neutral voltage displacement
 Two independent elements are supplied, each of
 which has a definite time delay element. These can
 be used to detect earth faults in high impedance
 earthed or isolated systems. For this feature, the
 residual voltage can be measured directly from an
 open delta tertiary winding or calculated internally
 from the three phase voltage inputs.
 These elements include a third harmonic filter,
 which de-sensitises the elements to any
 superimposed third harmonic frequencies.
 Underfrequency and overfrequency
 ARGUS 8 – 200/ 300 series only.
 Four independent elements are supplied, each of
 which can be set to operate for underfrequency or
 overfrequency and all having separate definite time
 delay elements. These can be applied wherever
 frequency protection is required to maintain system
 stability e.g. in load shedding schemes. The
 accuracy and security of operation of the numeric
 algorithms enables the relay to be employed to
 detect any frequency abnormalities.
 SYSTEM DATA
 ARGUS 8 variants with two voltage inputs have a ' 2
 Systems A/ B‘ connection setting. This allows two
 different systems each to be assigned two of the
 under/ overvoltage elements, using one of the
 voltage inputs for each system.
 This feature could be used as part of a local
 generation scheme with islanding capability, where
 one input is allocated to the local system, and the
 other to the grid.
 |